Brand: Nguồn điện liên tục - Opti UPS

DS-B 1-3KVA

An Online UPS is not a further improvement of the standby technology, but a completely different approach to providing the highest level of power supply. A double-conversion refers to converting the incoming AC power into DC power, and inverting it back to AC power. This ensures the newly reproduced power to be of a quality standard set by UPS, to be completely cleared of all imperfections of the power coming from the AC mains. Regardless of what is going on the AC mains side, the UPS output voltage, frequency and signal purity are kept up to the highest standards. The current flow is absolutely uninterruptible, the transfer time is zero. The UPS can work in pair with diesel generator, and can accommodate additional battery cabinets for a longer backup time. 

Beside those, the Durable Series UPS offer a set of essential features that make these UPS a flexible power supply control and power saving tool. 

By now the Durable Series UPS perfectly serve their purpose in numerous data processing, medical, banking and other mission critical centres around the globe.

Model Name DS1000B DS1500B DS2000B DS3000B
Topology True On-Line, Double Conversion, High Frequency
On-battery Output Waveform Pure Sine Wave
Maximum Capacity 1000VA / 700W 1500VA / 1050W 2000VA / 1400W 3000VA / 2100W
INPUT
Nominal Input Voltage 100 / 110 / 120Vac or 220 / 230 / 240Vac
Nominal Input Frequency 50Hz / 60Hz Auto Sensing
Input Voltage Range 80-144Vac (100 / 110 / 120Vac) or 160-276Vac (220 / 230 / 240Vac)
OUTPUT
Nominal Output Voltage 100 / 110 / 120 / 127Vac or 220 / 230 / 240Vac (selectable)
Output Voltage Regulation Rated Voltage ±2% (on battery)
Transfer Time (Typical) 0 ms
Start on Battery Yes
Auto Restart Yes
Number of Outlets 6 Battery backup (NEMA 15A) 12 Battery backup (NEMA 15A) 12 Battery backup (NEMA 15A)
4 Battery backup (IEC 10A) 9 Battery backup (IEC 10A×8 / 16A×1)
PROTECTION
Data Line Surge Protection RJ11 / RJ45
Surge Energy Rating 125 Joules (100 / 110 / 120Vac) or 280 Joules (220 / 230 / 240Vac)
Overload Protection UPS shuts down at 110% load after 10 secs or 130% load after 1.5 secs
Over Current Protection Circuit Breaker
Discharge Protection Keylock
BATTERY
Configuration 36V (12V 7.2AH×3) 36V (12V 34W×3) 72V (12V 7.2AH×6) 72V (12V 34W×6)
Backup Time (Full / Half load) 6 / 18 min 5 / 15 min 6 / 18 min 5 / 15 min
Recharge Time to 90% (Typical) < 4 Hours
Extended Battery Pack (Optional)* BP1000 BP1500 BP2000 BP3000
12V 7.2AH×6 12V 34W×6 12V 7.2AH×12 12V 34W×12
ADVANCED WARNINGS / DIAGNOSTICS
Front Panel AC mode / On line / On battery / Bypass / Fault / Overload and 15 UPS Status
Audible Alarms Battery mode / UPS faults / Overload
COMMUNICATION INTERFACE
Communication Port RS232 and USB#
SNMP Manageable Yes
ENVIRONMENTAL
Operation Temperature 0~40°C / 32~104°F
Storage Temperature -20~60°C / -4~140°F
Relative Humidity 0~95% Non condensing
Audible Noise <40dBA
PHYSICAL
Dimensions Physical / Packing (L×W×H ) in 16.5×6×9.4 / 21.5×11×14 16.5×8.9 ×14.1 / 20.7×13.8×19.1
mm 420×152×238 / 545×280×355 420×225×358 / 526×350×485
Weight (Net / Gross) lbs 36.4 / 40.6 37.7 / 41.9 68.5 / 74.1 72.8 / 78.3
kg 16.5 / 18.4 17.1 / 19 31.1 / 33.6 33 / 35.5
Battery Pack Physical / Packing (L×W×H ) in 16.5×6×9.4 / 21.5×11×14 16.5×8.9 ×14.1 / 20.7×13.8×19.1
mm 420×152×238 / 545×280×355 420×225×358 / 526×350×485
Battery Pack (Net / Gross) lbs 46.7 / 50 88.4 / 98.4
kg 21.1 / 22.6 40 / 44.5
CONFORMANCE
Approvals UL / cUL, CE, GOST-R
Share: